New Mexico Register / Volume
XXXIII, Issue 3 / February 8, 2022
This
is an amendment to 14.9.2 NMAC, amending part name and Sections 3, 5, 7, 8, 9,
10, 11, 12, 13, 14, 16, 20, 21 and 28, effective March 10, 2022
PART
2 [2015] 2021 NEW MEXICO
MECHANICAL CODE
14.9.2.3 STATUTORY
AUTHORITY: Sections 60-13-9, [and] 60-13-44, 60-13-45,
60-13-46 and 60-13-47 NMSA 1978.
[14.9.2.3 NMAC - Rp, 14.9.2.3 NMAC, 05/15/2018; A,
3/10/2022]
14.9.2.5 EFFECTIVE DATE: May 15, 2018, unless a later date is cited at the end of a section. From
the date of publication of this rule in the New Mexico register, until September
10, 2022, permits may be issued under either the previously adopted rule, or
this rule. After September 10, 2022, permits may be issued only under this
rule.
[14.9.2.5 NMAC -
Rp, 14.9.2.5 NMAC, 05/15/2018; A, 3/10/2022]
14.9.2.7 DEFINITIONS: See 14.5.1 NMAC, General
Provisions and Chapter 2 of the [2015] 2021 Uniform Mechanical Code
(UMC) as amended in 14.9.2.10 NMAC.
[14.9.2.7 NMAC -
Rp, 14.9.2.7 NMAC, 05/15/2018; A, 3/10/2022]
14.9.2.8 ADOPTION OF THE [2015] 2021 UNIFORM MECHANICAL CODE:
A. This rule adopts by reference the [2015]
2021 UMC, as amended by this rule.
B. In this rule, each provision is
numbered to correspond with the numbering of the [2015] 2021 UMC.
C. This rule shall apply in conjunction with
the provisions of all applicable New Mexico construction codes, laws and
standards.
[14.9.2.8 NMAC -
Rp, 14.9.2.8 NMAC, 05/15/2018; A, 3/10/2022]
14.9.2.9 CHAPTER 1 ADMINISTRATION: See this
chapter of the UMC except as provided below.
A. 101.0 General.
(1) 101.1 Title Delete this section of the UMC and
substitute: This code shall be known as
14.9.2 NMAC, the [2015] 2021 New Mexico Mechanical Code (NMMC).
(2) 101.2
Scope. Delete this section of the
UMC and see 14.9.2.2 NMAC.
(3) 101.3
Purpose. Delete this section of the
UMC and see 14.9.2.6 NMAC.
B. 102.0
Applicability. See this section of
the UMC except as provided below. 102.1
Conflicts between codes. Delete this section of the UMC and see [14.5.1
NMAC] Subsection H of Section 60-13-44 NMSA 1978
and 14.5.1.9 NMAC.
C. 103.0 Duties and powers of the authority
having jurisdiction.
(1) 103.1
General. Delete this section of the UMC and see Construction Industries Licensing
Act (CILA).
(2) 103.2 Liability. Delete this section of the UMC and see CILA
Section [60.13.26] 60-13-26 NMSA 1978.
(3) 103.3 Applications and permits.
Delete this section of the UMC and see14.5.2
NMAC.
(4) 103.4 Right of entry. Delete this section of the UMC and see CILA
Section [60.13.42] 60-13-42 NMSA 1978.
D. 104.0 Permits.
See this section of the [UPC] UMC except as provided
below.
(1) 104.1 Permits required. Delete this section of the UMC and see 14.5.2
NMAC.
(2) 104.2 Exempt work. See CILA Section 60-13-45 B NMSA
1978 and this
section of the UMC.
(3) 104.3 Application of permit. Delete this section of the UMC and see 14.5.2
NMAC.
(4) 104.4 Permit issuance. Delete this section of the UMC and see 14.5.2
NMAC.
(5) 104.5 Fees. Delete this section of the UMC and see 14.5.5
NMAC.
E. 105.0 Inspections and testing. Delete this section of the UMC and see 14.5.3
NMAC.
F. 106.0 Violations and penalties. Delete this section of the UMC and see CILA [Section
60.13.1 to 59] Sections 60-13-1 through 60-13-59 NMSA 1978, and
14.5.3 NMAC.
G. 107.0 Board of appeals. Delete this section of the UMC
and see [14.5.1] 14.5.1.13 NMAC.
H. Table 104.5 Mechanical permit fees. Delete this table from the UMC and see 14.5.5
NMAC.
[14.9.2.9 NMAC - Rp, 14.9.2.9 NMAC, 05/15/2018; A, 3/10/2022]
14.9.2.10 CHAPTER 2 DEFINITIONS: See this chapter of the UMC
except as provided below.
A. 203.0
Authority having jurisdiction.
Delete the text of this definition and substitute: The authority having
jurisdiction is the CID and the mechanical-plumbing trade bureau chief [of
the mechanical and plumbing bureau of CID] for adoption,
enactment, interpretation and enforcement of the state adopted mechanical code
as the minimum requirement in the state.
B. 214.0 Listed (Third
Party Certified). See this
definition in the [UPC] UMC and add the following provision at
the end of the definition: A manufacturer may select the independent
certification organization of its choice to certify its products, provided that
the certification organization has been accredited by the American national standards
institute (ANSI), or another certification organization that CID has approved
in writing.
C. 217.0
Occupiable Space. Delete this
section and see 14.7.2 NMAC and 14.7.3 NMAC.
[14.9.2.10 NMAC - Rp, 14.9.2.10 NMAC, 05/15/2018; A, 3/10/2022]
14.9.2.11 CHAPTER 3 GENERAL REQUIREMENTS: See this chapter of the UMC
except as provided below.
A. 304.3 Access to equipment and
appliances on roofs. 304.3.1 Access. See
this section of the UMC except after the words “in height” add the following:
except those designated as R-3 occupancies.
B. 305.1 Installation in garages. At the end of the last sentence delete the
following text: “unless listed as a flammable vapor ignition resistant.
C. 305.5
Drainage Pan. See this section of the UMC except after each term “water
heater” add the following: or hot-water-heating boiler.
[C] D. 311.0 Heating and cooling air system. See this section of the UMC except as
follows: 311.3 Prohibited source. See
this section of the UMC except delete the text of subsection (5) and replace
with the following: a closet, bathroom,
laundry room, toilet room, kitchen; or where it will pick up objectionable
odors, fumes, or flammable vapors.
[D] E. 314.0 Balancing. Delete this section of the UMC and insert:
Heating, ventilating, and air-conditioning systems (including hydronic systems)
shall be balanced in accordance with the standards pursuant to UMC chapter 17.
[14.9.2.11 NMAC - Rp, 14.9.2.11 NMAC, 05/15/2018; A, 3/10/2022]
14.9.2.12 CHAPTER 4 VENTILATION AIR: See this chapter of the UMC except as provided below.
A. 405.3 Bathroom Exhaust. See this section of the UMC except add the following:
Exception: Residential Occupancies with an operable
window located in the same room.
B. 405.4 Kitchen Exhaust. See this section
of the UMC except after the words “directly to the outdoors” add the following:
unless listed for recirculation.
[14.9.2.12 NMAC - Rp, 14.9.2.12 NMAC, 05/15/2018; A, 3/10/2022]
14.9.2.13 CHAPTER 5 EXHAUST SYSTEMS: See this chapter of the UMC
except as provided below. 511.3 Makeup [air] Air. See this section of the UMC except add the
following: windows and doors shall not
be used for the purpose of providing makeup air. The exhaust and makeup air systems shall be
connected by an electrical interlocking switch.
A device to sense continued air movement within the makeup air plenum
shall be installed initiating a complete system shut-down if air-flow is
interrupted.
[14.9.2.13 NMAC - Rp, 14.9.2.13 NMAC, 05/15/2018; A, 3/10/2022]
14.9.2.14 CHAPTER 6 DUCT SYSTEMS: See
this chapter of the UMC except as [follows] provided below.
A. [603.12]
603.11 Underground installation.
See this section of the UMC and add the following to the last sentence,
“and be installed so as to support the weight of the concrete during
encasement.”
B. [608.0]
609.0 Automatic shutoffs. [608.1]
609.1 Air-moving systems and smoke detectors. See this section of the UMC and add the
following to the exceptions: (6) automatic shutoffs are not required on
evaporative coolers that derive all of their air from outside the building.
[14.9.2.14 NMAC - Rp, 14.9.2.14 NMAC, 05/15/2018; A, 3/10/2022]
14.9.2.16 CHAPTER 8 CHIMNEYS AND [VENT LOCATIONS] VENTS: See this chapter of the UMC except as provided below. 803.1.10
Chimney and [vent locations] Vents. See this section of the UMC except delete
the following language: "Where
vents extend outdoors above the roof more than 5 feet (1524mm) higher than
required by Table [802.6.2] 802.6.1, and where vents terminate in
accordance with Section [802.6.2(1)] 802.6.1 (1)(b), the outdoor
portion of the vent shall be enclosed as required by this section for vents not
considered to be exposed to the outdoors or such venting shall be
engineered."
[14.9.2.16 NMAC - Rp, 14.9.2.16 NMAC, 05/15/2018; A, 3/10/2022]
14.9.2.20 CHAPTER 12 HYDRONICS: See this chapter of the UMC
except as provided below. 1205.2
Pressure testing. See this section
of the UMC except delete the first sentence and substitute: system piping shall be tested with a
hydrostatic pressure or an air test of not less than 1.5 times operating
pressure.
[14.9.2.20 NMAC - Rp, 14.9.2.20 NMAC, 05/15/2018;
A, 3/10/2022]
14.9.2.21 CHAPTER 13 FUEL GAS PIPING: See this chapter of the UMC
except as provided below.
A. 1308.5.2.2
Copper and copper alloy pipe. Delete this section and substitute
with the following: Copper and copper alloy pipe shall not be used. Aluminum
alloy pipe shall not be used with gases corrosive to such material.
[B. 1308.5.3.2
Copper and copper alloy. Delete this section and substitute with the
following: Copper and copper alloy pipe shall not be used. Aluminum alloy pipe
shall not be used with gases corrosive to such material].
[C] B. [1311.11.2] 1310.11.2 Emergency shutoff valves. See
this section of the UMC except delete the following: the emergency shutoff valves shall be plainly
marked as such and their locations posted as required by the authority having
jurisdiction. [See this section of
the UMC except add] Add the following to the end: For purposes of isolation and safety, an
additional approved gas shut off valve shall be installed
downstream of the serving supplier gas meter prior to any distribution of gas
into the gas piping system
[D] C. [1312.0] 1311.0 Electrical bonding and grounding. Delete this section of the UMC and see
[14.10.4] subsection G of 14.10.4.11 NMAC.
[E] D. [1313.9] 1312.11 Liquefied
petroleum gas facilities and piping. Delete this section of the [UPC]
UMC and substitute the following: Liquefied petroleum gas facilities
shall comply with [19.15.40 NMAC, liquefied petroleum gas standards, and]
Sections 70-5-1 [to -23] through
70-5-23 NMSA 1978, [liquefied and compressed gasses] the
LPG and CNG Act and with 19.15.40 NMAC liquefied petroleum gas standards.
[F] E. [1314.3] 1313.3 Test
pressure. See this section of the
UMC except add the following:
Exception: An existing gas piping
system may be tested at a test pressure equal to one and one-half times them
operating pressure of the system, but in no case shall it be tested at less
than 3 psi.
[14.9.2.21 NMAC - Rp, 14.9.2.21 NMAC, 05/15/2018; A, 3/10/2022]
14.9.2.28 [APPENDICIES] APPENDICES: See
this section of the UMC except
delete appendix A and appendix B.
[14.9.2.28 NMAC -
Rp, 14.9.2.28 NMAC, 05/15/2018; A,