TITLE 20 ENVIRONMENTAL
PROTECTION
CHAPTER 5 PETROLEUM STORAGE TANKS
PART 106 NEW AND UPGRADED UNDERGROUND STORAGE
TANK SYSTEMS: DESIGN,
CONSTRUCTION, AND INSTALLATION
20.5.106.1 ISSUING AGENCY: New Mexico Environmental
Improvement Board.
[20.5.106.1 NMAC
- N, 07/24/2018]
20.5.106.2 SCOPE: This part applies to owners and
operators of storage tanks as provided in 20.5.101 NMAC. If the owner and operator of a storage tank
are separate persons, only one person is required to comply with the
requirements of this part, including any notice and reporting requirements;
however, both parties are liable in the event of noncompliance.
[20.5.106.2 NMAC
- N, 07/24/2018]
20.5.106.3 STATUTORY AUTHORITY: This part is promulgated pursuant
to the provisions of the
Hazardous Waste
Act, Sections 74-4-1 through 74-4-14 NMSA 1978, and the general provisions of
the
Environmental
Improvement Act, Sections 74-1-1 through 74-1-17 NMSA 1978.
[20.5.106.3 NMAC
- N, 07/24/2018]
20.5.106.4 DURATION: Permanent.
[20.5.106.4 NMAC
- N, 07/24/2018]
20.5.106.5 EFFECTIVE DATE: July 24, 2018, unless a later date is
indicated in the bracketed history note at the end of a section.
[20.5.106.5 NMAC
- N, 07/24/2018]
20.5.106.6 OBJECTIVE: The purpose of 20.5.106 NMAC is
to set forth the requirements for the design, construction, installation and
upgrading of underground storage tank systems in a manner that will prevent
releases and to protect the public health, safety and welfare and the
environment of the state.
[20.5.106.6 NMAC
- N, 07/24/2018]
20.5.106.7 DEFINITIONS: The definitions in 20.5.101 NMAC
apply to this part.
[20.5.106.7
NMAC - N, 07/24/2018]
20.5.106.8 to 20.5.106.599 [RESERVED]
20.5.106.600 GENERAL PERFORMANCE STANDARDS FOR UST
SYSTEMS:
A. In order to prevent releases due to
structural failure, corrosion or spills and overfills for as long as a UST
system is used to store regulated substances, owners and operators of any UST
system shall:
(1) properly
design, construct, and initially test each new UST system;
(2) provide
project drawings to the bureau 30 days prior to installation; and
(3) ensure that any portion of a UST
system that routinely contains regulated substances and is in contact with the
ground, water, or other electrolyte shall be protected from corrosion, in
accordance with the current edition of an industry standard or code of practice
developed by a nationally recognized association or independent testing
laboratory approved in advance by the department.
B. Owners and operators shall ensure
that the entire UST system is compatible with any regulated substance conveyed,
as required by 20.5.107.708 NMAC.
C. Tanks and piping installed or
replaced after April 4, 2008 must be secondarily contained in accordance with
20.5.106.606 NMAC and use interstitial monitoring in accordance with
20.5.108.808 NMAC, 20.5.108.811 NMAC, and 20.5.108.813 NMAC, except for suction
piping that meets the requirements of Subsection B of 20.5.108.813 NMAC.
D. Secondary containment must be able
to contain regulated substances leaked from the primary containment until they
are detected and removed and prevent the release of regulated substances to the
environment at any time during the operational life of the UST.
[20.5.106.600
NMAC - N, 07/24/2018]
20.5.106.601 PERFORMANCE STANDARDS FOR
FIBERGLASS-REINFORCED PLASTIC USTS: If a
UST is constructed of fiberglass-reinforced plastic, owners and operators shall
comply with the requirements of the current edition of an industry standard or
code of practice developed by a nationally recognized association or
independent testing laboratory approved in advance by the department. Owners and operators shall use one or more of
the following to comply with the requirements of this section:
A. Underwriters Laboratories Standard 1316, “Glass-Fiber-Reinforced
Plastic Underground Storage Tanks for Petroleum Products, Alcohols, and
Alcohol-Gasoline Mixtures”; or
B. Underwriters’ Laboratories of Canada Standard 615, “Standard for Fibre Reinforced Plastic Underground Tanks for Flammable
and Combustible Liquids”.
[20.5.106.601
NMAC - N, 07/24/2018]
20.5.106.602 PERFORMANCE STANDARDS FOR STEEL USTS:
A. Owners and operators shall cathodically protect steel USTs by:
(1) coating the
tank with a suitable dielectric material;
(2) ensuring
that field-installed cathodic protection systems are designed by a corrosion
expert;
(3) designing and installing impressed current
or galvanic systems to allow ready determination of current operating status as
required in Subsection C of 20.5.107.705 NMAC; and
(4) operating
and maintaining cathodic protection systems in accordance with 20.5.107 NMAC.
B. If a UST is constructed of steel,
owners and operators shall comply with the requirements of the current edition
of an industry standard or code of practice developed by a nationally
recognized association or independent testing laboratory approved in advance by
the department. Owners and operators
shall use one or more of the following to comply with the applicable
requirements of this section:
(1) Steel Tank Institute, “STI-P3 Specification and Manual for External
Corrosion Protection of Underground Steel Storage Tanks”;
(2) Underwriters
Laboratories Standard 1746, “Standard
for External Corrosion Protection Systems for Steel Underground Storage Tanks”;
(3) Underwriters
Laboratories of Canada Standard 603,
“Standard for Steel Underground Tanks for Flammable and Combustible Liquids”;
(4) Underwriters
Laboratories of Canada Standard
603.1, “External Corrosion Protection Systems for Steel Underground
Tanks for Flammable and Combustible Liquids”;
(5) Underwriters’
Laboratories of Canada S631, “Standard
for Isolating Bushings for Steel Underground Tanks Protected with External Corrosion Protection Systems”;
(6) NACE
International Standard Practice
SP0285, “External Corrosion Control of Underground Storage Tank Systems
by Cathodic Protection”;
(7) Steel
Tank Institute Standard F841, “Standard for Dual Wall Underground Steel
Storage Tanks”; or
(8) Underwriters
Laboratories Standard 58, “Standard for Steel Underground Tanks
for Flammable and Combustible Liquids”.
[20.5.106.602
NMAC - N, 07/24/2018]
20.5.106.603 PERFORMANCE STANDARDS FOR USTS
CONSTRUCTED OF STEEL AND CLAD OR JACKETED WITH A NON-CORRODIBLE MATERIAL: If a UST is constructed of steel
and clad or jacketed with a non-corrodible material, owners and operators shall
meet the current edition of an industry standard or code of practice developed
by a nationally recognized association or independent testing laboratory
approved in advance by the department.
Owners and operators shall use one or more of the following to comply
with the requirements of this section:
A. Underwriters
Laboratories Standard 1746, “Standard
for External Corrosion Protection Systems for Steel Underground Storage Tanks”;
B. Steel
Tank Institute ACT-100® Specification
F894, “Specification for External Corrosion Protection of FRP Composite
Steel Underground Storage Tanks”;
C. Steel Tank Institute ACT-100-U®
Specification F961, “Specification for External Corrosion Protection of
Composite Steel Underground Storage Tanks”; or
D. Steel Tank Institute Specification
F922, “Specification for Permatank®”.
[20.5.106.603
NMAC - N, 07/24/2018]
20.5.106.604 PERFORMANCE STANDARDS FOR METAL USTS
WITHOUT CORROSION PROTECTION: If a
UST is constructed of metal without additional corrosion protection measures,
owners and operators shall only install the tank at a site that is approved in
writing in advance of installation by a corrosion expert not to be corrosive
enough to cause the UST to have a release due to corrosion during its
operational life. Owners and operators
shall maintain records that demonstrate compliance with this paragraph for the
remaining life of the tank.
[20.5.106.604 NMAC - N, 07/24/2018]
20.5.106.605 INSTALLATION OF UST SYSTEMS:
A. Owners and operators shall properly
install all USTs and piping:
(1) in accordance
with the current edition of an industry standard or code of practice developed
by a nationally recognized association or independent testing laboratory
approved in advance by the department; and
(2) in
accordance with the manufacturer's instructions.
B. Owners and operators shall use one
or more of the following to comply with the requirements of this section:
(1) American
Petroleum Institute RP 1615, “Installation
of Underground Hazardous Substances or Petroleum Storage Systems”;
(2) Petroleum
Equipment Institute Publication
RP100, “Recommended Practices for Installation of Underground Liquid
Storage Systems”; or
(3) National Fire Protection Association Standard 30, “Flammable and Combustible
Liquids Code” and Standard 30A, “Code for Motor Fuel Dispensing Facilities
and Repair Garages”.
[20.5.106.605 NMAC - N, 07/24/2018]
20.5.106.606 SECONDARY CONTAINMENT FOR UST SYSTEMS:
A. Owners and operators shall install
secondary containment as follows:
(1) for any new or replaced UST system;
(2) for any new
or replaced dispenser system. A
dispenser system is considered replaced when both the dispenser and the
equipment needed to connect the dispenser to the
underground storage tank system are installed at a
UST facility. The equipment necessary to connect the dispenser to the underground storage tank system includes check
valves, shear valves, unburied risers or
flexible connectors, or other
transitional components that are underneath
the dispenser and connect the dispenser to the underground
piping. Under-dispenser containment shall allow for
access to the components in the containment system for visual inspections; and
(3) for any UST piping replaced after April 4, 2008.
B. Owners and operators shall design,
provide project drawings for, and construct the entire new UST system with the
secondary containment system in compliance with the current edition of an
industry standard or code of practice developed by a nationally recognized
association or independent testing laboratory.
The project drawings shall be approved in advance by the
department. The secondary containment
system shall:
(1) include all
tanks, piping, dispenser systems, and all containment sumps for any piping and ancillary
equipment that routinely contains regulated substances;
(2) include containment sumps, including
under-dispenser containment, transition sumps, and containment sumps for
submersible turbine pumps, that are liquid-tight on their sides, bottoms, and
at any penetrations; and
(3) be
interstitially monitored in accordance with the requirements in 20.5.108 NMAC.
C. If owners and operators:
(1) replace a
UST, they shall install a double-walled tank with an inner and outer barrier
and a release detection system that meets the requirements of 20.5.108 NMAC;
(2) replace a dispenser system, they
shall install, in accordance with manufacturer's recommendations, an
under-dispenser containment system that shall be hydrostatically tested and
approved by the department prior to use; types of under-dispenser containment
systems include, but are not limited to, dispenser liners, containment sumps,
dispenser pans and dispenser sump liners; or
(3) replace
piping, they shall install only double-walled piping with an inner and outer
barrier and a release detection system that meets the requirements of 20.5.108
NMAC for the replaced piping.
D. Owners and operators shall use one
or more of the following to comply with secondary containment requirements:
(1) Petroleum
Equipment Institute Publication RP100,
“Recommended Practices for Installation of Underground Liquid Storage
Systems”;
(2) American
Petroleum Institute RP 1615, “Installation
of Underground Hazardous Substances or Petroleum Storage Systems”;
(3) National
Fire Protection Association Standard 30, “Flammable and
Combustible Liquids Code”; or
(4) National
Fire Protection Association Standard 30A, “Code for Motor Fuel
Dispensing Facilities and Repair Garages”.
E. The secondary containment requirements
of this section shall not apply to:
(1) existing
USTs in a manifolded system (as secondary containment is only required for a
new or replaced UST in a manifolded system);
(2) repairs meant
to restore a UST, piping or dispenser system to operating condition;
(3) piping runs
that are not new or replaced for USTs with multiple piping runs;
(4) suction
piping that meets the requirements of Subsection B of 20.5.108.813 NMAC; and
(5) non-pressurized piping that manifolds
two or more underground tanks together, such as a siphon piping system;
[20.5.106.606 NMAC - N, 07/24/2018]
20.5.106.607 PERFORMANCE
STANDARDS FOR EXISTING UST SYSTEMS:
A. All
existing UST systems (installed on or before December 22, 1988), by the
effective date of these regulations, must have complied with one of the
following requirements:
(1) new UST performance standards in 20.5.106 NMAC;
(2) upgrade requirements in Subsection B of 20.5.106.607 NMAC;
or
(3) closure requirements in 20.5.115 NMAC.
B. UST
upgrading requirements. Owners and
operators must have upgraded existing steel USTs by the effective date of these
regulations to meet one of the following requirements in accordance with the
current edition of an industry standard or code of practice developed by a
nationally recognized association or independent testing laboratory approved in
advance by the department. Steel USTs
that have not been upgraded by the effective date of these regulations shall be
immediately permanently closed in accordance with 20.5.115 NMAC.
(1) Internal
lining.
(a) USTs
upgraded by internal lining must meet the following:
(i) the lining was installed in
accordance with an industry standard or code of practice developed by a
nationally recognized association or independent testing laboratory that was
approved in advance by the department, and
(ii) within 10 years after installation of internal lining and
every five years thereafter, the lined UST is required to be internally
inspected in accordance with the current edition of an industry standard or
code of practice developed by a nationally recognized association or
independent testing laboratory, or manufacturer’s recommendation, approved in
advance by the department.
(b) One
of the following shall be used to comply with internal lining upgrading
requirements:
(i) National
Leak Prevention Association Standard
631, Chapter B, “Future Internal
Inspection Requirements for Lined Tanks”;
(ii) American Petroleum Institute Recommended Practice 1631, “Interior Lining and Periodic Inspection of
Underground Storage Tanks”; or
(iii) Ken Wilcox Associates Recommended Practice, “Recommended Practice for Inspecting Buried
Lined Steel Tanks Using a Video Camera”.
(c) Owners
and operators shall permanently close USTs in accordance with the requirements
of 20.5.115 NMAC if the internal lining is not performing in accordance with
the original design specifications and cannot be repaired in accordance with
one of the following codes:
(i) National
Fire Protection Association Standard
30, “Flammable and Combustible
Liquids Code”;
(ii) American Petroleum Institute Recommended Practice RP 2200, “Repairing Hazardous Liquid Pipelines”;
(iii) American Petroleum Institute Recommended Practice RP 1631, “Interior Lining and Periodic Inspection of
Underground Storage Tanks”;
(iv) National Fire Protection Association Standard 326, “Standard for the Safeguarding
of Tanks and Containers for Entry, Cleaning, or Repair” or;
(v) National Leak Prevention Association Standard 631, Chapter A, “Entry, Cleaning,
Interior Inspection, Repair, and Lining of Underground Storage Tanks”.
(2) Cathodic
protection. USTs upgraded by cathodic
protection shall meet the requirements of 20.5.106.602 NMAC and owners and
operators must have ensured the integrity of the tank by:
(a) performing
internal inspections and assessments to ensure that the tank was structurally
sound and free of corrosion holes prior to installing the cathodic protection
system; or
(b) if the tank had been installed for less than 10 years, by
either having monitored monthly for releases in accordance with 20.5.108 NMAC
or by having assessed for corrosion holes by conducting two tightness tests
that met the requirements of 20.5.108 NMAC and that were approved in advance by
the department. Owners and operators
must have conducted the first tightness test prior to installing the cathodic
protection system. Owners and operators
must have conducted the second tightness test between three and six months
following the first operation of the cathodic protection system.
(c) Owners
and operators shall use one or more of the following to comply with cathodic
protection upgrade requirements:
(i) Steel
Tank Institute Recommended Practice
R972, “Recommended Practice for the Addition of Supplemental Anodes to STI-P3®
USTs”;
(ii) NACE International Standard Practice SP0285, “External Corrosion Control of Underground
Storage Tank Systems by Cathodic Protection”; or
(iii) American Petroleum Institute Publication RP 1632, “Cathodic Protection of
Underground Petroleum Storage Tanks and Piping Systems”.
(3) Internal
lining combined with cathodic protection.
USTs upgraded by internal lining combined with cathodic protection must
have met the following:
(a) the lining was installed in accordance with the current
edition of an industry standard or code of practice developed by a nationally
recognized association or independent testing laboratory, as follows:
(i) National
Leak Prevention Association Standard
631, Chapter B, “Future Internal Inspection Requirements for Lined Tanks”;
(ii) American Petroleum Institute Recommended Practice 1631, “Interior Lining
and Periodic Inspection of Underground Storage Tanks”;
(iii) National
Fire Protection Association Standard
326, “Standard for the Safeguarding of Tanks and Containers for Entry,
Cleaning, or Repair”, or
(iv) National Leak Prevention Association Standard 631, Chapter A, “Entry, Cleaning,
Interior Inspection, Repair, and Lining of Underground Storage Tanks”; and
(b) the cathodic protection meets the requirements of
20.5.106.602 NMAC and has complied with one of the following:
(i) Steel
Tank Institute Recommended Practice
R972, “Recommended Practice for the Addition of Supplemental Anodes to
STI-P3®USTs”; or
(ii) NACE International Standard Practice SP0285, “External Control of Underground Storage Tank
Systems by Cathodic Protection”; or
(iii) American Petroleum Institute Publication RP 1632, “Cathodic Protection of
Underground Petroleum Storage Tanks and Piping Systems”.
C. Piping
upgrade requirements.
Owners and operators shall cathodically protect
and upgrade metal piping in existing UST systems that routinely contain
regulated substances and are in contact with an electrolyte, such as soil, to
meet the requirements of 20.5.106.609 NMAC or 20.5.106.610 NMAC.
D. Spill
and overfill prevention equipment.
Owners and operators shall comply with the spill and overfill prevention
requirements in 20.5.106.613 NMAC.
Owners and operators of existing UST systems who installed oil/water
separators to meet spill prevention requirements shall discontinue their use in
meeting these requirements and shall install new spill prevention equipment
that meets the requirements in Subsection F of 20.5.106.613 NMAC no later than
three years after the effective date of these regulations.
E. Owners
and operators of existing fiberglass reinforced plastic UST systems may install
an internal lining in order to address compatibility issues in accordance with Fiberglass Tank and Pipe Institute Recommended Practice T-95-1,
“Remanufacturing of Fiberglass Reinforced Plastic (FRP) Underground Storage
Tanks”.
[20.5.106.607 NMAC - N, 07/24/2018]
20.5.106.608 GENERAL PERFORMANCE STANDARDS FOR
PIPING:
A. Owners and
operators shall properly design and construct new piping, provide project
drawings, initially test piping, and ensure that any steel portion of piping
that routinely contains regulated substances and is in contact with an
electrolyte, such as soil or water, shall be protected from corrosion, in
accordance with the current edition of an industry standard or code of practice
developed by a nationally recognized association or independent testing
laboratory approved in advance by the department. Owners and operators shall use one or more of
the following to comply with the requirements of this section:
(1) third party certification from a nationally recognized
laboratory;
(2) American Society of Mechanical Engineering
Standard B31.3, “Process Piping”;
(3) American Society of Testing and Materials
A53, “Standard Specification for Pipe,
Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless”;
(4) American Society of Testing and Materials
A106, “Standard Specification for
Seamless Carbon Steel Pipe for High-Temperature Service”; or
(5) American Society of Testing and Materials
A135, “Standard Specification for
Electric-Resistance-Welded Steel Pipe”.
B. Owners and
operators shall ensure that piping is compatible with any regulated substance
conveyed in accordance with 20.5.107.708 NMAC.
C. Owners and
operators shall protect all piping from impact, settlement, vibration,
expansion, corrosion, and damage by fire.
D. Owners and
operators shall install a containment sump at any point where piping
transitions from above the surface of the ground to below the ground surface.
E. If owners and
operators install more than one type of piping at an underground storage tank
system, then owners and operators shall comply with the requirements applicable
to each type of piping for that run of piping.
[20.5.106.608
NMAC - N, 07/24/2018]
20.5.106.609 PERFORMANCE STANDARDS FOR PIPING
CONSTRUCTED OF NON-CORRODIBLE MATERIAL:
A. If owners and
operators construct or operate piping of fiberglass-reinforced plastic or
flexible piping, the piping shall:
(1) be completely underground;
(2) be within secondary containment that includes a release
detection system that meets the requirements of 20.5.108 NMAC;
(3) have a suitable cover approved by the piping manufacturer;
or
(4) have equivalent protection approved by the piping
manufacturer and approved by the department prior to installation.
B. Owners and operators shall ensure
that the piping meets the requirements of the current edition of an industry
standard or code of practice developed by a nationally recognized association
or independent testing laboratory approved in advance by the department, and
that the piping is approved by the manufacturer for the application for which
it is to be used. Owners and operators
shall use one or more of the following to comply with the requirements of this
section:
(1) Underwriters Laboratories Standard 971, “Standard for Nonmetallic
Underground Piping for Flammable Liquids”; or
(2) Underwriters Laboratories of Canada Standard S660, “Standard for Nonmetallic
Underground Piping for Flammable and Combustible Liquids”.
[20.5.106.609
NMAC - N, 07/24/2018]
20.5.106.610 PERFORMANCE STANDARDS FOR STEEL PIPING
FOR UST SYSTEMS:
A. If owners and
operators construct or operate piping of steel for a UST system, owners and
operators shall:
(1) coat the piping with a suitable dielectric material;
(2) field-install
a cathodic protection system designed by a corrosion expert; and
(3) design any impressed current system to allow ready
determination of current operating status as required in Subsection C of 20.5.107.705
NMAC.
B. Owners and
operators shall ensure that the piping meets the requirements of the current
edition of an industry standard or code of practice developed by a nationally
recognized association or independent testing laboratory approved in advance by
the department, and that the piping is approved by the manufacturer for the
application for which it is to be used.
Owners and operators shall use one or more of the following to comply
with the requirements of this section:
(1) American Petroleum Institute Recommended Practice 1632, “Cathodic
Protection of Underground Petroleum Storage Tanks and Piping Systems”;
(2) Underwriters Laboratories Subject 971A, “Outline of Investigation for
Metallic Underground Fuel Pipe”;
(3) Steel Tank Institute Recommended Practice R892, “Recommended
Practice for Corrosion Protection of Underground Piping Networks Associated
with Liquid Storage and Dispensing Systems”;
(4) NACE International Standard Practice SP0169, “Control of External Corrosion on Underground
or Submerged Metallic Piping Systems”; or
(5) NACE International Standard Practice SP0285, “External Corrosion Control of Underground
Storage Tank Systems by Cathodic Protection”.
C. If owners and
operators construct piping of steel for a UST system without additional
corrosion protection measures, owners and operators shall only install the
piping at a site that is approved, in writing, in advance of installation, by a
corrosion expert, to not be corrosive enough to cause the piping to have a release
due to corrosion during its operational life.
Owners and operators shall maintain records that demonstrate compliance
with this requirement for the remaining life of the piping.
D. If owners and
operators install or operate steel piping above ground that connects to an
emergency generator or loading rack, they shall:
(1) meet the requirements in Subsection D of 20.5.106.608 NMAC;
(2) meet the requirements in Subsection A of 20.5.106.610 NMAC;
and
(3) meet the requirements in 20.5.109.915 NMAC for the above
ground steel portion of the piping.
[20.5.106.610
NMAC - N, 07/24/2018]
20.5.106.611 UNDERGROUND
STORAGE TANK SYSTEMS AT MARINAS:
A. Owners
and operators of underground storage tank systems at marinas shall install an
automatic break-away device to shut off flow of fuel from on-shore piping,
which shall be located at the connection of the on-shore piping and the piping
leading to the dock. Owners and
operators shall install another automatic break-away device to shut off flow of
fuel located at any connection between flexible piping and hard piping on the
dispenser system and dock. The automatic
break-away devices shall be easily accessible, and their location shall be
clearly marked.
B. Owners
and operators of underground storage tank systems at marinas shall electrically
isolate dock piping where excessive stray electrical currents are encountered.
C. Owners
and operators of underground storage tank systems at marinas shall protect
piping from stress due to tidal action.
D. Owners
and operators shall use Petroleum
Equipment Institute Publication
RP1000, “Recommended Practices for the Installation of Marina Fueling Systems”,
or, if applicable, the current edition of an industry standard or code of
practice developed by a nationally recognized association or independent
testing laboratory approved in advance by the department.
[20.5.106.611 NMAC - N, 07/24/2018]
20.5.106.612 VENTING
FOR UNDERGROUND STORAGE TANK SYSTEMS:
A. Owners
and operators shall design and construct venting for all underground storage
tank systems, following the current edition of an industry standard or code of
practice developed by a nationally recognized association or independent
testing laboratory approved in advance by the department.
B. Vent
pipes that are provided for normal tank venting shall be located so that the
discharge point is outside of buildings higher than the fill pipe opening. Vent pipes shall be installed not less than
15 feet from power ventilation air intake devices and not less than five feet
from a building opening. Vent outlets
and devices shall be designed and installed to minimize blockage.
C. Types
of vent pipes.
(1) Vent
pipes that are provided for normal tank venting shall extend at least 12 feet
above ground level.
(2) If
attached to a structure, vent pipes shall extend at least 5 feet above the
highest projection of the canopy or roof.
(3) Vent
pipes for normal tank venting shall be of appropriate size for the capacity and
operating conditions of the tank.
D. Owners
and operators shall use one of more of the following to comply with the
requirements of this section:
(1) Petroleum Equipment Institute Publication RP100, “Recommended Practices
for Installation of Underground Liquid Storage Systems”;
(2) National Fire Protection Association Standard 30, “Flammable and Combustible Liquids Code”;
(3) National Fire Protection Association Standard 30A, “Code for Motor Fuel Dispensing Facilities and Repair Garages”;
(4) Underwriters Laboratories Standard 142, “Standard for Steel
Aboveground Tanks for Flammable and Combustible Liquids”; or
(5) International Code Council, "International Fire Code”.
[20.5.106.612 NMAC - N,
07/24/2018]
20.5.106.613 SPILL AND OVERFILL PREVENTION:
A. Except as provided in subsection B
of this section, to prevent spilling and overfilling associated with transfers
of regulated substances to underground storage tank systems, owners and operators
shall use the following spill and overfill prevention equipment:
(1) spill
prevention equipment that will prevent release of regulated substances to the
environment when the transfer hose is detached from the fill pipe; and
(2) overfill
prevention equipment for USTs that will:
(a) automatically
shut off flow into the tank when the tank is no more than ninety-five percent
full; or
(b) alert the
transfer operator when the tank is no more than ninety percent full by restricting
the flow into the tank or triggering a high-level audible alarm.
B. Owners and operators are not
required to use the spill and overfill prevention equipment specified in
Subsection A of this section if approved in writing in advance by the department
where:
(1) alternative equipment is used that is
determined by the department to be no less protective of public health, safety
and welfare and the environment than the equipment specified in Paragraphs (1)
and (2) of Subsection A of this section; or
(2) the
underground storage tank system is filled by transfers of no more than 25
gallons at one time;
C. Flow restrictors
or ball float valves used in vent lines shall not be used as overfill
prevention equipment for USTs when overfill prevention is installed or replaced
after[the effective date of these rules.
D. Spill and
overfill prevention equipment must be periodically tested or inspected in
accordance with 20.5.107.704 NMAC.
E. Owners
and operators of UST systems with remote fill piping shall install a trap door
or equivalent device and shall meet the following:
(1) Flow
restrictors or ball float valves shall not be installed or used on a UST system
with a remote fill pipe.
(2) Owners
and operators who install or modify remote fill piping shall install a
containment sump where remote fill piping connects to the UST.
F. Overfill
prevention and spill prevention equipment for new UST systems shall be either
listed in accordance with an
industry standard or code of practice developed by a nationally recognized
association or independent testing laboratory for use with
flammable and combustible liquids.
G. Owners
and operators shall not install oil/water separators to meet spill prevention
requirements for UST systems.
[20.5.106.613
NMAC - N, 07/24/2018]
20.5.106.614 LOADING RACKS:
A. Owners and operators who install
loading racks shall design and construct them in accordance with the current
edition of an industry standard or code of practice developed by a nationally
recognized association or independent testing laboratory approved in advance by
the department. Owners and operators
shall use one or more of the following to comply with the requirements in this
section:
(1) American
Petroleum Institute Standard 2610, “Design, Construction, Operation, Maintenance
& Inspection of Terminal and Tank Facilities”;
(2) National
Fire Protection Association Standard
30, “Flammable and Combustible Liquids Code”;
(3) International
Code Council, “International Fire Code”; or
(4) Petroleum
Equipment Institute RP 800, “Recommended Practices for Installation of
Bulk Storage Plants.”
B. Owners
and operators of aviation fuel storage tank systems who install loading racks
shall comply with National Fire Protection Association Standard 407,
“Standard for Aircraft Fuel Servicing”.
C. Owners and operators shall install a
containment system that is designed to contain all releases of regulated
substances that occur during loading and unloading operations at the loading
rack. For all loading racks, owners and
operators shall install either:
(1) a drainage system, or secondary
containment system meeting the requirements of 20.5.106 NMAC, with a catchment
basin capable of containing the largest compartment of a tank car or tanker
truck that is loaded or unloaded at the facility; or
(2) a drainage system that is connected to a treatment facility
designed to receive releases of regulated substances that occur during loading
and unloading operations.
D. Owners and operators shall ensure that
loading racks are at least 25 feet from ASTs containing class I liquids (such
as gasoline), buildings, and property lines.
Owners and operators shall ensure that loading racks are at least 15
feet from ASTs containing class II or class III liquids.
[20.5.106.614
NMAC - N, 07/24/2018]
20.5.106.615 REQUIRED NOTIFICATION PRIOR TO
INSTALLATION: To
ensure that an inspector has an opportunity to be present during the steps in
procedures which are important to the prevention of releases, owners, operators,
and certified tank installers shall give the department notice of the dates on
which critical junctures in the installation of an underground storage tank
system are to take place. The inspector
may require that critical junctures be performed from Monday through Friday
during regular business hours.
A. For
installations, the term “critical junctures” means:
(1) preparation of the excavation immediately prior to receiving
backfill and a UST or piping for a UST;
(2) installation of any tank pad, vault, or secondary
containment for a storage tank system;
(3) setting of a storage tank and piping, including placement of
any anchoring devices, backfill to the level of the tank, and strapping, if
any;
(4) placing a regulated substance in the tank;
(5) any time during the installation in which components of
piping are connected;
(6) all pressure testing or integrity testing of an underground
storage tank system, including associated piping, performed during the
installation; and
(7) completion of backfill and filling of the excavation.
B. Owners,
operators and certified tank installers shall give at least 30 days written
notice before the installation of an underground storage tank system. At a minimum, the installation notice shall
contain the following information:
(1) date the form is completed;
(2) facility name, facility ID number, address (with county),
and telephone number;
(3) owner name, owner ID number, address, and telephone number;
(4) contractor name, address, and telephone number;
(5) tank details (number and size, type and materials, products
to be stored);
(6) piping material and type of leak detection;
(7) type of spill and overfill prevention;
(8) type of corrosion protection (sacrificial, impressed current,
or none with explanation why corrosion protection not required);
(9) method of leak detection (statistical inventory
reconciliation, automatic tank gauges, visual, vapor monitoring, interstitial
monitoring, inventory control with tightness testing);
(10) approximate date installation will take place; and
(11) the signature of the owner or owner's representative filling
out the form.
C. Owners,
operators and certified tank installers shall provide required project drawings
with the 30 day written notice.
D. In addition to
the written notice described in this section, owners, operators and certified
tank installers shall give oral notice at least 24 hours in advance of the
commencement of the procedure. In the
oral notice, owners, operators and certified tank installers shall describe any
changes to the 30-day written notice required in Subsection B of this section,
such as different equipment or installation methods.
E. If owners,
operators and certified tank installers are separate persons, only one person
is required to comply with the notice requirements of this section; however,
all parties are liable in the event of noncompliance.
[20.5.106.615
NMAC - N, 07/24/2018]
[The department
provides an optional form that may be used for notification of installation.
The form is available
on the petroleum
storage tank bureau’s pages on the department’s website or by contacting the
Petroleum Storage Tank Bureau at 505-476-4397 or 2905 Rodeo Park Drive East,
Building 1, Santa Fe, New Mexico 87505.]
20.5.106.616 REQUIRED CERTIFICATIONS:
A. Certification of compliance. All owners and operators of new underground
storage tank systems shall certify in the registration form required by
20.5.102 NMAC compliance with the following requirements:
(1) installation
of tanks and piping in 20.5.106.605 NMAC for UST systems;
(2) cathodic
protection of steel tanks and piping in 20.5.106.602 NMAC and 20.5.106.610 NMAC
for UST systems, or 20.5.106.604 NMAC for UST systems;
(3) financial
responsibility under 20.5.117 NMAC; and
(4) release
detection in 20.5.108 NMAC.
B. Installer certification. All owners and operators of new underground
storage tank systems shall ensure that the installer certifies in the
registration form required by 20.5.102 NMAC that the methods used to install
the storage tanks and piping comply with the requirements in 20.5.106 NMAC.
C. Certification of installation. Owners and operators shall demonstrate
compliance with the installation standards in 20.5.106 NMAC. Owners and operators shall provide a
certification of installation on the UST registration form required by 20.5.102
NMAC, which asserts that all of the following methods of certification,
testing, and inspection were used to demonstrate compliance with installation
requirements of the UST system:
(1) the
installer has been certified by the tank and piping manufacturers;
(2) the
installer has been certified or licensed as required in 20.5.105 NMAC; and
(3) the
installer has notified, submitted required documentation to, and the
installation has been inspected by the department; and
(4) all work
listed in the manufacturer’s installation checklists has been completed.
[20.5.106.616
NMAC - N, 07/24/2018]
20.5.106.617 ALTERNATE METHODS:
A. If owners and operators want to install
tanks, piping, underground storage tank systems, spill and overfill equipment,
secondary containment, or any other requirement of this part with materials or
methods that are not in accordance with the current edition of an industry
standard or code of practice developed by a nationally recognized association
or independent testing laboratory, owners and operators shall apply in writing
to the department, shall provide supporting documentation, and shall not begin
the installation unless and until the department approves the request in
writing. At a minimum, the request for
an alternate method shall contain the following:
(1) date the
form is completed;
(2) facility
name, facility ID number, address (with county) and telephone number;
(3) owner name,
owner ID number, address and telephone number;
(4) citation to
regulation for which alternate method or material (such as type of piping) is
requested;
(5) brief
description of the proposed alternate method or material;
(6) justification
of proposed alternate method or material, including citation to a standard or
code supporting its use, if available; and
(7) demonstration
of its equivalent protection of public health, safety and welfare and the
environment.
B. The department shall not grant the
request unless owners and operators demonstrate that the request will provide
equivalent protection of public health, safety and welfare and the environment.
[20.5.106.617
NMAC - N, 07/24/2018]
[The department
provides an optional form that may be used to request approval of an alternate
method. The form is available on the petroleum storage tank bureau’s pages on
the department’s website or by contacting the Petroleum Storage Tank Bureau at
505-476-4397 or 2905 Rodeo Park Drive East, Building 1, Santa Fe, New Mexico
87505.]
HISTORY OF
20.5.106 NMAC:
Pre-NMAC
History: The
material in this part was derived from that previously filed with the
commission of
public
records - state records center and archives.
EIB/USTR-4, Underground
Storage Tank Regulations - Part IV - New and Upgraded UST Systems: Design,
Construction,
and Installation, filed 9/12/88
EIB/USTR-4,
Underground Storage Tank Regulations - Part IV - New and Upgraded UST
Systems: Design,
Construction,
and Installation, filed 8/4/89
EIB/USTR-4,
Underground Storage Tank Regulations - Part IV - New and Upgraded UST
Systems: Design,
Construction,
and Installation, filed 6/12/90
History of
Repealed Material: 20 NMAC 5.4, Underground Storage Tanks,
New and Upgraded UST Systems:
Design,
Construction, and Installation (filed 2/27/97), repealed 8/15/03.
20.5.4 NMAC,
Petroleum Storage Tanks, New and Upgraded Tank Systems: Design, Construction and Installation
(filed 7/16/03) repealed 4/4/08.
20.5.4 NMAC,
Petroleum Storage Tanks, New and Upgraded Tank Systems: Design, Construction and Installation
(filed 4/4/08) repealed 07/24/2018.
Other History:
EIB/USTR-4,
Underground Storage Tank Regulations - Part IV - New and Upgraded UST
Systems: Design,
Construction,
and Installation (filed 6/12/90), renumbered, reformatted and replaced by 20
NMAC 5.4, New and
Upgraded UST
Systems: Design, Construction, and
Installation, effective 11/5/95.
20 NMAC 5.4,
Underground Storage Tanks, New and Upgraded UST Systems: Design, Construction, and
Installation
(filed 10/6/95) replaced by 20 NMAC 5.4, New and Upgraded UST Systems: Design, Construction, and
Installation,
effective 4/1/97.
20 NMAC 5.4,
Underground Storage Tanks, New and Upgraded UST Systems: Design, Construction, and
Installation
(filed 2/27/97) was renumbered, reformatted and replaced by 20.5.4 NMAC, New
and Upgraded Tank
Systems: Design,
Construction and Installation, effective 08/15/03.
20.5.4 NMAC,
Petroleum Storage Tanks, New and Upgraded Tank Systems: Design, Construction and Installation
(filed 8/15/03) was replaced by 20.5.106 NMAC, Petroleum
Storage Tanks, New and Upgraded Underground Storage Tank Systems: Design,
Construction and Installation, effective 07/24/2018.